The fuse holder features a stainless-steel tab (Flipper) which, together with a spring, prevents the fuse link from being subjected to tensile forces greater than 3 kgf during the closing operation.
This mechanism also allows the fuse link to be quickly expelled from the cartridge during low-current faults, eliminating the possibility of internal arcs.
The internal coating not only enhances the durability of the fuse holder tube but also helps extinguish the electric arc caused by the fuse link burning.
The Maurizio fuse holder model is specifically designed to facilitate installation and removal using insulated switch rods.
It can be opened using a load-opening device and is interchangeable with fuse switch bases from other manufacturers that meet the same technical specifications.
This product is suitable for electrical networks with voltages ranging from 15 kV to 38 kV, ensuring broad applicability across various electrical network configurations.
Designed in accordance with ABNT, ANSI, and IEC standards.